2.0 Design • Vacuum Pump Application
Vacuum Pump Application
• The vacuum pump vent length must be from 2 ft. to 25 ft.
• The maximum number of elbows in the vent system is two.
• Both isolation boots provided with the system must be installed prior to the vacuum pump (Figure 3.2).
Vacuum pump selection is based on the overall BTU/H input of each system. Refer to Chart 2.3 for
vacuum pump determination.
Example:
A system designed with one HLV-150 burner and two HLV-100 burners has an overall system input
of 350,000 BTU/h. This system requires the PB-9 vacuum pump as indicated in Chart 2.3.
Model
No.
Total System Input
Range (BTU/h)
Allowable Burners
per Pump Weight
Dimensions
(See Figure 2.11)
A B C
NC-7
40,000 to 150,000 1 min. / 2 max. 20 lbs. 10.0” 16.0” 18.5”
PB-8
50,000 to 275,000 1 min. / 4 max. 60 lbs. 11.0” 19.75” 16.5”
PB-9
280,000 to 545,000 2 min. / 6 max.* 67 lbs. 14.5” 19.75” 16.5”
PB-10A
550,000 to 750,000 3 min. / 6 max.* 73 lbs. 17. 5 ” 21.0” 20.0”
Chart 2.3 • Vacuum Pump Models
Figure 2.11 • Vacuum Pump Dimensions
(see chart 2.3)
B
C
B
NC-7 Pump • Side View NC-7 Pump • Front View PB Series Pumps • Isometric View
* Consult factory if exceeding maximum burners is required.
NOTE: The average sound level of PB Series vacuum pumps is between 60 and 63 DBA. If the
application requires a lower decibel level, relocation of the vacuum pump or a sound-deadening enclosure
may be necessary. Contact factory.