18
HLV Series
C
A
2.0 Design • Vacuum Pump Application
Vacuum Pump Application
The vacuum pump vent length must be from 2 ft. to 25 ft.
The maximum number of elbows in the vent system is two.
Both isolation boots provided with the system must be installed prior to the vacuum pump (Figure 3.2).
Vacuum pump selection is based on the overall BTU/H input of each system. Refer to Chart 2.3 for
vacuum pump determination.
Example:
A system designed with one HLV-150 burner and two HLV-100 burners has an overall system input
of 350,000 BTU/h. This system requires the PB-9 vacuum pump as indicated in Chart 2.3.
Model
No.
Total System Input
Range (BTU/h)
Allowable Burners
per Pump Weight
Dimensions
(See Figure 2.11)
A B C
NC-7
40,000 to 150,000 1 min. / 2 max. 20 lbs. 10.0 16.0 18.5
PB-8
50,000 to 275,000 1 min. / 4 max. 60 lbs. 11.0 19.75” 16.5
PB-9
280,000 to 545,000 2 min. / 6 max.* 67 lbs. 14.5 19.75” 16.5
PB-10A
550,000 to 750,000 3 min. / 6 max.* 73 lbs. 17. 5 21.0 20.0
Chart 2.3 • Vacuum Pump Models
Figure 2.11 • Vacuum Pump Dimensions
(see chart 2.3)
B
C
B
NC-7 Pump Side View NC-7 Pump Front View PB Series Pumps Isometric View
* Consult factory if exceeding maximum burners is required.
NOTE: The average sound level of PB Series vacuum pumps is between 60 and 63 DBA. If the
application requires a lower decibel level, relocation of the vacuum pump or a sound-deadening enclosure
may be necessary. Contact factory.