High humidity or saltwater atmospheres will accelerate heater corrosion and reduce useful life. Do not
install the heater in locations where water (in the form of rain, drips, or spray) could fall onto the gas
ignition components.
The suspension of the heater must conform to all applicable codes referenced in the safety section and
these instructions.
To ensure proper operation, the heater must be installed in a level horizontal position. The units are
designed to be hung with threaded rod via the four (4) threaded inserts on the top panel of the heater.
1
Determine desired mounting points, and mark the locations for the hanging points.
2
Prepare the mounting surface. If necessary, weld blocks, drill holes, or install additional bracketing
or steel channel.
3
Fasten beam clamp, screw hook, turnbuckle, steel channel, or other anchoring device to the
suspension points.
4
Determine the desired mounting height. Cut four pieces of 3/8”-16 threaded rod of equal length in
which the heater will be hung from. Ensure that the threads are not damaged during the cutting
process.
5
Using 3/8-16 threaded rod, thread a nut up one end at a distance of approximately 1 inch. This is
the end that will be screwed into the heater.
6
Next, place a lock washer on top of the nut and thread the rod assembly into the unit heater’s
threaded inserts. A minimum of 2-3 complete threads must be exposed on the reverse side of the
threaded insert (approx. 9-10 turns), but no more than 20 turns, as this may cause the threaded rod
to collide with or damage the heat exchanger.
7
Tighten down the previously installed jam nuts to prevent the threaded rod from turning.
8
Attach threaded rod to prepared anchoring device. Adjust the threaded rod until the unit is level and
equal weight distribution is achieved. Threaded rod must be perpendicular with the unit. Do not
install threaded rods at an angle, as this can result in weakened structural integrity or undue noise.
3.0 Installation
3.0 Installation
WARNING
!
Improper suspension of the unit heater may result in collapse and being crushed.
Always suspend from a permanent part of the building structure that can evenly
support the total force and weight of the heater.
Failure to maintain minimum clearance to combustibles may result in fire and/ or
explosion, property damage, serious injury or death. Always maintain minimum
clearances.